6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 623 -
Output signal to BO
The SPOS01 function, in Figure 4.1-4, can issue a “Select success” signal at the output point
“SPOS01_FSL_BO_CSF” when the SPOS01 function determines that the Select command Off
(Remote-OFF-Control) signal is true. If the SPOS01 function determines that the Remote-
OFF-Control signal is not true, the SPOS01 function returns to the Wait for a command
stage.
(iii) Receiving “Selection command On” from the local-end
Figure 4.1-5 outlines the reception of the selection command On from the local-end.
Signal reception
from the front panel
Select command On from front panel
Signal output
Select
decision
Success
Failed
Selection logic
Selection logics
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Off from remote-end
Select command Off from front panel
Select command On by the PLC
Select command Off by the PLC
Select command On from remote-end
Figure 4.1-5 Outline of selection commandOn
Input signal generated at the local-end.
Figure 4.1-6 shows the select logic when a “Select command On (Local-ON-Control)” signal is
applied to the SPOS01 function. The signal is provided when an On key is pressed on the
IED front panel; the user is not required to map the signal from the IEC61850 communication.
Note that the user should set the scheme switch [SPOS01-CTRAHMI] to SBO when operation
from the IED front panel is required; we discuss how to set this in chapter
User interface:
Control sub-menu
.