4.4.4 Mapping for IEC61850 communication
The user can operate the OPTIM function over the IEC61850 communication after the
mapping using the GR-TIEMS. Note that the OPTIM function is designed for “Single Point
Controller (SPC) class in the IEC61850 communication. The user should follow steps:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data
(i) Editing Logical Node
The user should make a logical node (LN) for the OPTIM function. Figure 4.4-12 exemplifies
LN editing; the LN General Input / Output (GGIO) is chosen for the OPTIM function. After
the user defining an object SPCSO, the OPTIM logical node can be saved with the name
GIGO plus LN Instance”. Make a definition of the object SPCSO in the OPTIM logical node.
Either the SBO mode or the DIR mode can be chosen in the LN editing.
SBO defined in LN
Figure 4.4-12 Defining “SPCSOobject in GIGO3302 logic node