Toshiba GR200 Series - (iii) Setting example 3 (Bus-bar VT=Phase-C, Line VT= Three-phase)

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 486 -
(iii) Setting example 3 (Bus-bar VT=Phase-C, Line VT= Three-phase)
VCT
V
a
V
c
Vs
V
b
Line VT
(Three phase)
Bus-bar VT
(Phase C)
Line
Bus-bar
b. Phasor diagram in Bus-bar
a. Phasor diagram in line
V
a
(V
L1
)
V
b
(V
L2
)
V
c
(V
L3
)
Vs (V3)
Vs2 (V4)
V
Bus-bar
(Vs)
2
V
Line
(V
c
)
1
Figure 2.35-8 Example 3: Input voltages and respective phasor diagram for SYN1
1
Note: V
Bus-bar
is Running voltage.
2
Note: V
Line
is Incoming voltage.
The configuration of inputs voltages and phases is done as shown in Figure 2.35-8. In
this case, configure the settings in accordance with Figure 2.35-8 and Table 2.35-9.
Table 2.35-9 Setting for example 3
Output voltage at VT
Bus-bar VT= Phase-C
Line VT= Three phase
Input voltage at VCT
Running voltage (Vs)= Phase-C (Bus-bar VT)
Incoming voltage (V
c
)= Phase-C (Line VT)
VCHK Setting
[SYN-VBus] = V3
[SYN-VLine]= V-L3
1
1
Note: Set V-L3 for the scheme switch [SYN-VLine]. This is because V3 and V-L3 are in
the same phase.