6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1418 -
FUN
Function type (FUN) applied to a command response frame is set referring to Table 11.4-13.
The FUN can be set to 0 to 255. When clicking the Change all FUNs on the Common
setting screen, all FUNs are changed to the setting values at Common setting.
DCO/Sig Off Name, Signal Off Desc., DCO Signal On Name, Signal On Desc.,
Inverse
Sig off and Sig On are used to set the Data ID of control object in General command.
(Hereafter, these are described as command output signal.) Inverse is used to reverse
the logic when controlling the command output signal.
When the command output signal is treated as two signals (Sig Off Sig On), the
control scheme is shown as the following table by the combination of the receiving command
DCO and Inverse setting.
For example, when the DCO=Off command is received under Inverse no-checked,
the command output signal of Sig Off is controlled to 1. Sig On is not controlled.
Table 11.4-13 Control Scheme of Command Output Signal (Sig Off Sig On)
“Inverse” checked
Control object
Receiving
command DCO
Checked
No-checked
Signal specified
to Sig.off
Signal specified
to Sig.on
Signal specified
to Sig.off
Signal specified to
Sig.on
Off
Controlled to “1”
Not controlled
Controlled to “0”
Not controlled
On
Not controlled
Controlled to “1”
Not controlled
Controlled to “0”
When the command output signal is treated as one signal (Sig Off = Sig On), the
control scheme is shown in Table 11.4-14. For example, when the DCO=On command is
received under Inverse checked, the command output signals of Sig On and Sig Off are
controlled to 0. Sig On is not controlled.
Table 11.4-14 Control Scheme of Command Output Signal (Sig Off = Sig On)
“Inverse” checked
Control object
Receiving
command DCO
Checked
No-checked
Signal specified
to Sig.off
Signal specified
to Sig.on
Signal specified
to Sig.off
Signal specified
to Sig.on
Off
Controlled to “0”
Controlled to ”1”
On
Controlled to ”1”
Controlled to “0”
When setting the Sig Off, Sig On and Inverse, check the specifications of the
command output signals of communication and others, and then set them.
Valid time