EasyManua.ls Logo

Toshiba GR200 Series - (iv) Receiving “Operate command Off” from the local-end; (iv)-1 Input signal generated at the local-end; (iv)-2 Output signal to BO

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 870 -
††
Note: To identify the input and output signal-points of the other DPOS logics, see Table
4.8-14 for PLC#1, Table 4.8-15 for PLC#2, Table 4.8-18 and Table 4.8-20 for output
signals.
‡‡
Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].
(iv) Receiving “Operate command Off” from the local-end
Figure 4.8-25 outlines the reception of the operate command Off from the local-end.
Signal reception from
the front panel
Operate command Off from the local-end
Do nothing
Operate
decision
Success
Failed
Operate logic
Wait for a command
Signal output
Operate command On from the local-end
Operate command Off from remote-end
Operate command On by the PLC function
Operate command Off by the PLC function
Wait for a next command
Select stage
Select command Off from the remote-end
Select command On from the remote-end
Select command Off from the local-end
Select command On from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Operate command On from remote-end
Figure 4.8-25 Outline of Operate command ‘Off’
Input signal generated at the local-end
Figure 4.8-26 illustrates the operate logic when an Operate command Off (Local-OFF-Control)
signal is applied to the DPOS01 logic. The input signal is provided when Execution for Off is
keyed on the IED front panel.
Output signal to BO
The DPOS01 function, in Figure 4.8-26, can issue an Operate” signal at the output point
DPOS01_FEX_BO”, when the DPOS01 function determines that the input signal Local-Off-
Control is true.

Table of Contents

Related product manuals