6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 272 -
2.17.7 Setting
OCN(Function ID:443001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
OCN1-EN
Off / On
-
OCN1 protection scheme switch
Off
OCN2-EN
Off / On
-
OCN2 protection scheme switch
Off
OCN3-EN
Off / On
-
OCN3 protection scheme switch
Off
OCN4-EN
Off / On
-
OCN4 protection scheme switch
Off
OCN1
OCN1-Dir
NonDir / Forward /
Reverse
-
OCN1 directional characteristic
NonDir
Fwd/
OCN1-Angle
0 - 180
deg
OCN1 directional characteristic angle
45
Rev
OCN1-Vpol
0.5 - 25.0
V
OCN1 polarizing voltage level
3.0
OCN1-Timer
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
IEEE-EI / US-CO2 /
US-CO8 / Original
-
OCN1 delay type
DT
DT
OCN1
0.02 -
50.00
0.10 -
250.00
A
OCN1 threshold (in DT mode)
0.40
2.00
OCN1-DPR
10 - 100
%
OCN1 drop-out/pick-up ratio
100
TOCN1
0.00 - 300.00
s
OCN1 operating delay time
1.00
IEC
OCN1
0.02 -
5.00
0.10 -
25.00
A
OCN1 threshold (in IDMT mode)
0.40
2.00
OCN1-DPR
10 - 100
%
OCN1 drop-out/pick-up ratio
100
OCN1-TMS-
IEC
0.010 - 50.000
-
OCN1 time multiplier of IEC inverse curve
1.000
TOCN1R
0.00 - 300.00
s
OCN1 definite time reset delay
0.00
UK
OCN1
0.02 -
5.00
0.10 -
25.00
A
OCN1 threshold (in IDMT mode)
0.40
2.00
OCN1-DPR
10 - 100
%
OCN1 drop-out/pick-up ratio
100
OCN1-TMS-
UK
0.010 - 50.000
-
OCN1 time multiplier of UK inverse curve
1.000
TOCN1R
0.00 - 300.00
s
OCN1 definite time reset delay
0.00
IEEE
OCN1
0.02 -
5.00
0.10 -
25.00
A
OCN1 threshold (in IDMT mode)
0.40
2.00
OCN1-DPR
10 - 100
%
OCN1 drop-out/pick-up ratio
100
OCN1-TMS-
IEEE
0.010 - 50.000
-
OCN1 time multiplier of IEEE inverse curve
1.000
OCN1-Rtimer
DEF / DEP
-
OCN1 reset delay type of IEEE
DEF
TOCN1R
0.00 - 300.00
s
OCN1 definite time reset delay
0.00
OCN1-RTMS-
IEEE
0.010 - 50.000
-
OCN1 dependent reset time multiplier of
IEEE inverse curve
1.000
US
OCN1
0.02 -
5.00
0.10 -
25.00
A
OCN1 threshold (in IDMT mode)
0.40
2.00
OCN1-DPR
10 - 100
%
OCN1 drop-out/pick-up ratio
100
OCN1-TMS-US
0.010 - 50.000
-
OCN1 time multiplier of US inverse curve
1.000
OCN1-Rtimer
DEF / DEP
-
OCN1 reset delay type of US
DEF
TOCN1R
0.00 - 300.00
s
OCN1 definite time reset delay
0.00
OCN1-RTMS-
US
0.010 - 50.000
-
OCN1 dependent reset time multiplier of US
inverse curve
1.000
ORG
OCN1
0.02 -
5.00
0.10 -
25.00
A
OCN1 threshold (in IDMT mode)
0.40
2.00
OCN1-DPR
10 - 100
%
OCN1 drop-out/pick-up ratio
100
OCN1-TMS-
ORG
0.010 - 50.000
-
OCN1 time multiplier of US inverse curve
1.000
OCN1-Rtimer
DEF / DEP
-
OCN1 reset delay type of ORG
DEF