6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 751 -
SOFTSW1 function (Function ID: 522001)
ON to OFF
Operate Command
Operate condition
ASEQ function§ is in progress
ASEQ_MULTI_SEL
&
&
Input
Output
Operate logic in SOFTSW1
S4301_FEC_CHG_PLC
(522001_8C0A041F5D)
522001_830A041D02
&
S4301_ST_OFF
Operate completed
S4301_PLC_CTRL_FAIL
(522001_870A041F62)
Operate failed
d
S4301_CHG_TO_OFF
522001 860A04EDE0
ON-control command
(PLC connection point #2)
S4301_EX_SS
(522001_870A041F62)
1.0s
0
t
Figure 4.3-20 ‘Off Operation logic using PLC logic
Note: To identify the input and output signal-points of the other SOFTSW logics, see
Table 4.3-4, Table 4.3-13, Table 4.3-14, Table 4.3-16, and Table 4.3-18.
Note: operate condition signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note: The ASEQ function can provide sequential signals for automatic control.
(vii) Operate condition
Figure 4.3-21 shows the operate condition logic of the SOFTSW1 function. The SOFTSW1
function can examine an operate-condition using Command Blocking signal
1
.
operate condition
SOFTSW1 function (Function ID: 522001)
Same Directional
Controlling Event
To operate logic
Control hierarchy (e.g. 43RL) (PLC connection point #3)*6
IED serious error detected
[S4301-EN]
On
Users must setup this condition correctly
Function Automatic sequence control is in progress
CBK_STATE
Command blocking*1 (defined as CBK)
Double Command Blocking detected*2
Other devices traveling detected*3
Tripping *4 (“General trip”)
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
GEN.TRIP
S4301_CTRL_RIGHT
522001 820A04ED50
SERI_ERR
Command ON control received
Command OFF control received
received
S4301_STATE
&
&
&
&
1
Unmatched condition detected *5
(522001 000A041001)
Figure 4.3-21 Operate condition logic for ON/OFF in SOFTSW1
*7
1
Note: “Command Blocking” disables any operation except for itself; See the signal
“S4301_STATE (Table 4.3-2)” as the state of “Command Blocking” in the SOFTSW
function.