6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 454 -
(ix) TPAR logic – settings (TTPAR1, TRR1)
The TPAR logic for CB#1 and CB#2 are illustrated in Figure 2.34-19. To operate in the TPAR
mode in the CB#1, the VCHK function provides a permission signal for the TPAR logic. The
dead timer [TTPAR1] is required to set in the logic. The user should set the [TRR1] to have the
coordination with the [TTPAR1].
For Issuing for CB
ARC1_TPAR_COND
TTPAR1
t 0
0.01 300.00 s
&
1
&
8000011B63
ARC1_TPAR
From Condition in CB#1
ARC1-S1 IN-PROG
TPAR1_START
810001EBBD
TPAR1_COND
810001EBBE
TPAR1_SUB_START
810001EBBF
TPAR1_SUB_COND
810001EBC0
&
&
TTPAR1_SUB
t 0
0.01 300.00 s
&
ARC1-VCHK
From VCHK function
For Issuing for CB
ARC2_TPAR_COND
TTPAR2
t 0
0.01 300.00 s
&
1
&
8100021B64
ARC2_TPAR
From Condition in CB#2
ARC2-S1 IN-PROG
TPAR2_START
810002EBBE
TPAR2_COND
810002EBBF
TPAR2_SUB_START
810002EBC0
TPAR2_SUB_COND
810002EBC1
&
&
TTPAR2_SUB
t 0
0.01 300.00 s
&
TPAR1_START
From Reclose sequence
ARC2-VCHK
TPAR2_START
From Initiation
From Initiation
TRR1
t 0
0.01 310.00 s
TRR2
t 0
0.01 310.00 s
ARC1 IN-PROG
CB1_94TT
CB2_94TT
To TRC
ARC1-S1 TRR
ARC2 TRR
ARC1-FT
ARC2-FT
Figure 2.34-19 ARC1 TPAR and ARC2 TPAR
Note: Settings [TTPAR1_SUB], [TTPAR2_SUB] are not required as in the default.