2.25.5 Setting
UVS(Function ID: 471101)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
BLK
UVSBLK-EN
Off / On
-
Operation canceled when UVSBLK operated
Off
UVSBLK
5.0 20.0
V
Threshold of UVSBLK element
10.0
TUVBLK
0.00 300.00
s
UVSBLK operation delay timer
10.00
UVS1-EN
Off / On
-
UVS1 protection scheme switch
Off
UVS2-EN
Off / On
-
UVS2 protection scheme switch
Off
UVS1
UVS1-Timer
DT / IDMT / Original
-
UVS1 delay type
DT
DT
UVS1
5.0 - 130.0
V
UVS1 threshold
60.0
UVS1-DPR
100 - 120
%
UVS1 drop-out/pick-up ratio
100
TUVS1
0.00 - 300.00
s
UVS1 operating delay time (in DT mode)
1.00
IDMT
UVS1
5.0 - 130.0
V
UVS1 threshold
60.0
UVS1-DPR
100 - 120
%
UVS1 drop-out/pick-up ratio
100
UVS1-TMS
0.010 - 100.000
-
UVS1 time multiplier (in IDMT mode)
1.000
TUVS1R
0.0 - 300.0
s
UVS1 definite time reset delay
0.0
ORG
UVS1
5.0 - 130.0
V
UVS1 threshold
60.0
UVS1-DPR
100 - 120
%
UVS1 drop-out/pick-up ratio
100
UVS1-TMS
0.010 - 100.000
-
UVS1 time multiplier (in ORG mode)
1.000
TUVS1R
0.0 - 300.0
s
UVS1 definite time reset delay
0.0
Output
UVS1-VTFBlk
Non / Block
-
UVS1 operation block by VTF
Non
UVS1-UseFor
Trip / Alarm
-
UVS1 used for trip or alarm
Trip
UVS2
UVS2-Timer
DT / IDMT / Original
-
UVS2 delay type
DT
DT
UVS2
5.0 - 130.0
V
UVS2 threshold
60.0
UVS2-DPR
100 - 120
%
UVS2 drop-out/pick-up ratio
100
TUVS2
0.00 - 300.00
s
UVS2 operating delay time (in DT mode)
1.00
IDMT
UVS2
5.0 - 130.0
V
UVS2 threshold
60.0
UVS2-DPR
100 - 120
%
UVS2 drop-out/pick-up ratio
100
UVS2-TMS
0.010 - 100.000
-
UVS2 time multiplier (in IDMT mode)
1.000
TUVS2R
0.0 - 300.0
s
UVS2 definite time reset delay
0.0
ORG
UVS2
5.0 - 130.0
V
UVS2 threshold
60.0
UVS2-DPR
100 - 120
%
UVS2 drop-out/pick-up ratio
100
UVS2-TMS
0.010 - 100.000
-
UVS2 time multiplier (in ORG mode)
1.000
TUVS2R
0.0 - 300.0
s
UVS2 definite time reset delay
0.0
Output
UVS2-VTFBlk
Non / Block
-
UVS2 operation block by VTF
Non
UVS2-UseFor
Trip / Alarm
-
UVS2 used for trip or alarm
Trip
Test tool(Function ID: 471101)
Item
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Function test
UVS-Test
Off / On
-
Not to execute UVSBLK element
Off