4.9.1 Select logic for SBO/DIR modes
The user should set scheme switch [TPOS01-CTREN] to On prior to TPOS01 operation. Table
4.9-11 shows all of the scheme switches in the TPOS function.
(i) Receiving “select command P1-control” from the remote-end
Figure 4.9-2 outlines the reception of the select command P1-control from the remote-end.
Signal reception
IEC61850
P1 control from the remote-end
Signal output
Select
decision
Success
Failed
Selection logic
P3 control from the remote-end
P1 control from the local-end
P2 control from the local-end
P3 control from the local-end
P1 control by the PLC function
P2 control by the PLC function
P3 control by the PLC function
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
P2 control from the remote-end
Figure 4.9-2 Outline of select command P1-control’
Input point required mapping
Figure 4.9-3 shows the select logic when a “Selection command (Remote-P1-Control)” signal is
applied to the TPOS01 function. This logic has the input-point “DEV01_CONTROL_REQ” for
the reception of a select command; the input-point should be mapped for IEC 61850
communication. The function will fail to operate if mapping is not performed correctly. We will
discuss how to map the input-points for IEC 61850 communication in section 4.9.7.