EasyManua.ls Logo

Toshiba GR200 Series - (ii)-2 Compensation; (iii) Data recording trigger and calculation trigger

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 389 -
symmetrical components, as shown in Figure 2.32-2. For further information, see
section 2.32.6(iii).
2
Note: In the calculation of earth fault, user is required to set the R
0
and the X
0
with
settings [FL_1R0] and setting [FL_1X0] respectively, when the impedance of line
GJ is considered in symmetrical components.
3
Note: When the mutual impedance of line GJ is considered , and when parallel lines are
applied, user should set the R
0m
and the X
0m
with settings [FL_1R0m] and
setting [FL_1X0m] respectively,. If a single line is considered, user are not
required to set these settings.
4
Note: User should set the K
a
, K
b
and K
c
with settings [FL_Ka], [FL_Kb], and [FL_Kc],
when the imbalance impedance is considered. For further information, see section
2.32.6(vi).
5
Note: User should set the line length for settings [FL_1line_km] when the length of line
GJ is considered and when the unit of length is represented by kilometer, as
shown in Figure 2.32-2. For further information, see section 2.32.6(v).
Compensation
Consider the influence of the distributed capacitance in Equation (2.32-23), likewise section
2.32.2(i)-2. When the line length is beyond 100km, the result of Equation (2.32-23) requires
compensation. Thus, Equation (2.32-17) is used to find the compensated distance () with
respect to the fault distance () which Equation (2.32-23) calculates. The setting procedures
are discussed later. (See section 2.32.6(iii)-2)
(iii) Data recording trigger and calculation trigger
The calculation is started by signals; and following protection functions provide the trigger
signals:
(a) Distance protection
1
(ZS/ZG)
(b) Over current protection
2
(OC)
(c) Current differential protection (DIFL)
(d) External protection
3
1
Note: For more information of the ZS/ZG, see Chapter
Relay application: Distance
protection
.
2
Note: For more information of the OC, see Chapter
Relay application: Overcurrent
protection
.
3
Note: With regard to the trigger signal from the external protection function, user can
program this trigger signal by using Element IDs (PLC connection points), as
shown in Table 2.32-3, which are also listed in section 0.

Table of Contents

Related product manuals