6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 78 -
Note: For more information, see
Chapter Relay application: Communication application
.
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].
Reception of remote-DIFGL-operation signal
Figure 2.7-8 shows the RDIF reception logic for the DIFLG function: PLC connection point
R1.DIFGL_OP is provided for the signal reception from the Remote-1_relay, another PLC
connection point R2.DIFGL_OP is provided for the Remote-2_relay. The receipt signals of
both remote-relays are ORed; then they are ANDed with the local DIFGL operation signal
when the user set On for scheme switch [DIFGL-RDIF-EN]. Finally, the RDIF function begins
to issue a trip signal. The SCOM4-SA1 in the sub-communication channel is applied.
R1.DIFGL_OP
800000EBB5
8000001BB5
R2.DIFGL_OP
810000EBB6
8100001BB6
1
Local DIFGL logic
DIFGL-RDIF-EN
On
DIFGL.RDIF_BLOCK
810000EBB1
8100001BB1
DIFGL_BLOCK
8F0000EBB2
8F00001BB2
1
1
&
&
R1 channel being in sound
&
R2 channel being in sound
&
0.00 to 300.00s
t 0
&
1
DIFGL-TRIP
8000001B23
To TRC
&
DIFGLFS_OP
From Fail-safe of DIFGL
DIFGL-INST_OP
800000EBB3
8000001BB3
TDIFGL
DIFGL-TP_BLOCK
800000EBB0
8000001BB0
EXECUTE-NORM-R2
1
800001C23
800001B62
Figure 2.7-8 Reception of remote operation signal in RDIF