Toshiba GR200 Series - 2.34.5 Autoreclosing logics; (i) Setting logic for ARC1 mode - setting (ARC1-MODE)

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 443 -
GEN.TRIP
ARC1 IN-PROG
ARC1-S1 IN-PROG
ARC1 SHOT1
Dead time [TTPAR1]
ARC1 CLOSE
COMMAND
[TCCW1]
)
CB#1 Status
Closed
Open
ARC1 CLOSE SUCCESS
ARC1 CLOSE FAIL
CB1 ALLPH
CLOSE
Fault current
ARC1 FT
ARC1-S2 IN-PROG
ARC1 SHOT2
ARC1-S3 IN-PROG
ARC1 SHOT3
[TCCW1]
)
[TCCW1]
)
Relay operation
Operated
Issued
Dead time [TD_MS2]
Dead time [TD_MS3]
Closed
Open
Lock out
Figure 2.34-10 Multi shot scheme [ARC-NUM]=S3 for a Permanent fault
Note:
1. The permissive signal ‘ARC1-VCHK’ is required for ARC SHOT1 operation, but has
been omitted for clarity in this figure.
2. ‘ARC1-VCHK’ permissive signal is introduced automatically in the TPAR mode. For
ARC-SHOT2 and onwards, the user must introduce the permissive signal from the
VCHK function by using PLC programming.
2.34.5 Autoreclosing logics
(i) Setting logic for ARC1 mode – setting (ARC1-MODE)
The ARC1-MODE input setting is illustrated in Figure 2.34-11. The scheme switch [ARC1-
MODE] has seven setting modes as OFF, FT, SPAR, TPAR, SPAR&TPAR, MPAR, and Original.