6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1382 -
11.3.10 Setting
Setting of 61850(Function ID: 301001)
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
GOINT
1 to 120
sec.
Maximum GOOSE resend interval
2
850BLK
Off/On
IEC 61850 enable/disable
Off
850AUT
Off/On
Authentication of IEC 61850 association
Off
850KEEPALIVE
1 to 120
sec.
TCP KeepAlive time for IEC 61850
20
TCMD
Off/On
Set T in CommTerm as actual Time
Off