6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 893 -
Setting for “Operate command On
Similarly, the point BO3-RB must be applied for the setting [DPOS01-OEXBORD].
Operate logic in
DPOS01
&
Signal designated by
setting [DPOS01-OEXBORD]
BO3circuit at
IO#1
Contact health check
logic in DPOS01
Result of contact health check
DPOS01_OEX_BO
510001_8201011DD3
BO3-RB
200B01_8202021113
Connection made by the user
Figure 4.8-47 Example connection of “Operate command On” for the health check feature
Setting for “Operate command Off”
Similarly, the point BO4-RB must be applied for the setting [DPOS01-FEXBORD].
Operate logic in
DPOS01
&
Signal designated by
setting [DPOS01-FEXBORD]
BO4 circuit at
IO#1
Contact health check
logic in DPOS01
Result of contact health check
DPOS01_FEX_BO
512001 8103011DD0
BO4-RB
200B01_8302031113
Connection made by the user
Figure 4.8-48 Example connection of “Operate command Off” for the health check feature