The signals assigned to GGIO1 variables are published automatically by default.
The GGIO1 data set is fixed and is pre-configured in GOOSE Publish screen. If
the user assign signals to other GGIO variables (for example, GGIO2, GGIO3) for
GOOSE publish operation, then the user needs to add those variables in the
GOOSE Publish screen.
Figure 11.3-20 shows the GOOSE Publish screen, where “System” is fixed and is
not configurable for GGIO1, whereas Ctrl(Control) and Prot(Protection) are
configurable. The user can add new variables from the Logical Node screen to
the GOOSE Publish screen using drag & drop* method. Figure 11.3-20 shows an
example for GOOSE Publish, where System/GGIO2$Ind1$stVal is added to the
GOOSE Publish screen.
*Note: Only stVal and q variables can be added to GOOSE Publish screen.