Setting for the contact health check (normal setting, example #1)
Figure 4.8-49 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1 to BO4 contacts. To check that the contact health check function is working
correctly, the respective points of the BO-RBs should be connected as shown in Table 4.8-29, to
demonstrate that the settings are physically matched with the BO contacts.
Table 4.8-29 Setting example for contact health check
Example #1
Contact health check settings for example #1
DPOS01_OSL_BO_FLG is connected to BO1 at IO#1
200B01 8002001113(BO1-RB) set for [DPOS01-OSLORD]
OK
DPOS01_FSL_BO_FLG is connected to BO2 at IO#1
200B01 8102011113 (BO2-RB) set for [DPOS01-FSLBORD]
OK
DPOS01_OEX_BO_CSF” is connected to BO3 at IO#1
200B01 8202021113(BO3-RB) set for [DPOS01-OEXBORD]
OK
DPOS01_FEX_BO_CSF” is connected to BO4 atIO#1
200B01 8302031113(BO4-RB) set for [DPOS01-FEXBORD]
OK
Plus (+)
DPOS01_OSL_BO_FLG
(512001 8603011DC6)
SW1 driven with
BO1 at IO#1
BO1
Drivers
Select command On
BO1-RB
(200B01_8002001113)
BO3
DPOS01_OEX_BO
(512001 8203011DD3)
BO4-RB
(200B01_8302031113)
BO4
DPOS01_FEX_BO
(512001 8103011DD0)
BO3-RB
(200B01_8202021113)
SW2 driven with
BO2 at IO#1
SW4 driven with
BO4 at IO#1
Remote/Local-end
SW 3
SW 1
Minus ()
BIO module
43SW
On
command
BO2
DPOS01_FSL_BO_FLG
(512001 8A03011DC4)
BO2-RB
(200B01_8102011113)
SW 2
SW 4
SW3 driven with
BO3 at IO#1
Select command Off
Operate command On
Operate command Off
Off
command
Figure 4.8-49 Contact health check setting and 43SW scheme for example #1