EasyManua.ls Logo

Toshiba GR200 Series - 5.4.6 Settings of binary input circuits; (i) Setting table (IO_SLOT1) at IO#1 (Function ID: 200 B01); (i)-1 For the standard type being furnished; (i)-2 For the variable type being furnished

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1074 -
5.4.6 Settings of binary input circuits
(i) Setting table (IO_SLOT1) at IO#1 (Function ID: 200B01)
For the standard type being furnished
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
Common
THRES_Lvl
Low / High
-
Determination of input threshold
Low
CMP_NUM
4 - 9
-
Number of times filtered
4
BI1
BI1_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
BI2
BI2_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
……
……
……
……
……
BI32
BI32_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
For the variable type being furnished
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
Common
THRES_Lvl
Low / High
-
Determination of input threshold
Low
THRES_Grp1
10 - 220
V
Threshold through BI1 to BI3
Applicable only in BI-2 module and
BIO-4 module
75
THRES_Grp2
10 - 220
V
Threshold through BI4 to BI6
Applicable only in BI-2 module and
BIO-4 module
75
THRES_Grp3
10 - 220
V
Threshold through BI7 to BI9
Applicable only in BI-2 module and
BIO-4 module
75
THRES_Grp4
10 - 220
V
Threshold through BI10 to BI12
Applicable only in BI-2 module and
BIO-4 module
75
CMP_NUM
4 - 9
-
Number of times filtered
4
BI1
BI1_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
BI2
BI2_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
……
……
……
……
……
BI12
BI12_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal

Table of Contents