6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 283 -
2.18.4 Setting
THM (Function ID: 451001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
THM-EN
Off / On
-
Thermal protection scheme switch
Off
THM
0.40 -
2.00
2.00 -
10.00
A
Thermal overload current
1.00
5.00
TTHM
0.5 - 500.0
min
Thermal time constant
10.0
Type
THM-Itype
Max phase/
Equivalent
-
Selection of THM equations
Equivalent
THM-q
0 - 10
-
Factor when Equivalent selected
0
SW
THMT-EN
Off / On
-
Thermal protection
Off
THM-UseFor
Trip / Alarm
-
THM used for trip or alarm
Trip
ALM
THMA-EN
Off / On
-
Thermal alarm switch
Off
THM-Alarm
50 - 100
%
Thermal alarm level multiplier
80
Test tool(Function ID: 451001)
Items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Function test
THM-Test
Off / On
-
Thermal protection scheme switch
Off
THM-IP
0.00 -
1.00
0.00 -
5.00
A
Thermal overload current
0.00
0.00