6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 785 -
IED
TOTALTIM
Binary IO module (BIO)
Photo-
coupler
Operating signal #12
Filter
BI12-NC
BI12
BI12-CPL
Device
Contact-switch
IED
front
screen
IED
screen
CPL
Device #12
Device #2
Device #1
Operating signal #2
Operating signal #1
Photo-
coupler
Filter
BI1-NC
BI1
BI1-CPL
CPL
Photo-
coupler
Filter
BI2-NC
BI2
BI2-CPL
CPL
PLC
TT01
PLC
TT02
TOTAL02_PLC_SGNL
TOTAL01_PLC_SGNL
PLC
TT12
TOTAL12_PLC_SGNL
SAS
Figure 4.5-2 Acquisition of operation signals
(iii) Setting for the report (Dead band)
For sending data for the network, the TOTALTIM function will get a new accumulated data
every cycle that is defined with the setting [TTIM*-SDB]. For example, if the user wishes to
report the operation time about the device #1, the user should set 1 to the setting [TTIM01-
SDB], provided the report cycle is required every one second.
Table 4.5-2 Setting for data revision
Scheme switch
Set
Comment
TTIM01-SDB
1 to 720sec
Data revision period for operating signal 1
TTIM02-SDB
1 to 720sec
Data revision period for operating signal 2
(omitted)
(omitted)
(omitted)
TTIM12-SDB
1 to 720sec
Data revision period for operating signal 12
(iv) Data correction
In the TOTALTIM function the user can correct the accumulation time using either IED front
panel operation or GR-TIEMS operation (For IED screen operation, see Chapter
User interface
.
For GR-TIEMS operation, see Chapter
Engineering tool
)