6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 848 -
(iv) Receiving “Select command Off” from the local-end
Figure 4.8-7 outlines the reception of the Select command Off from the local-end.
Signal reception
from the front panel
Select command Off from the local-end
Signal output
Select
decision
Success
Failed
Select logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command On from the remote-end
Select command On from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Select command Off from the remote-end
Figure 4.8-7 Outline of Select command ‘Off’
Input signal generated at the local-end
Figure 4.8-8 shows the Select logic when a “Select command Off (Local-OFF-Control)” signal
is received is applied to the DPOS01 function. The signal is provided when the user presses
the OFF key on the IED front panel; the user is not required to map the signal from IEC61850
communication.
Output signal to BO
When the select condition” signal is true, the DPOS01 function can issue a “Select success”
signal at the output-point DPOS01_FSL_BO_FLG.
1
Note: The signal DPOS01_FSL_BO_FLG is the same as the signal shown in Figure
4.8-4. If the signal Local-OFF-Control” is not true, the DPOS01 function returns
to the Wait for a command stage.