6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 849 -
Input
Output
Selection logic in DPOS01
Command Local-Off-Control
1≥
[DPOS01-CTRAHMI]
SBO
DPOS01 function (Function ID: 512001)
SBO
DIR
&
&
1≥
&
0.1s
0
0.6s
0
DPOS01-Open
ILK condition (“Off”) passed
ILK bypassing
ICB_STATE
Either SBO mode or DIR mode
(e.g., “ctlmodel” in IEC61850*)
Automatic sequence control function (AQEQ)§ in progress
ASEQ_MULTI_SEL
t
t
DPOS01_FSL_BO_FLG
(512001_8A03011DC4)
Select “Failed
To BO connection
Select success
To Wait for a command
Select condition
Select command
with ILK condition
Operate command
with ILK condition
For SBO operation
For DIR operation
Figure 4.8-8 Select ‘Off on the front panel in DPOS01
††
Note: The ILK function provides the operation criteria for “Off”.
Note: Aselect condition signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
.
††
Note: To identify the output signals of the other DPOS logics, see Table 4.8-9.