EasyManua.ls Logo

Toshiba GR200 Series - 4.2.8 Setting

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 727 -
4.2.8 Setting
DPSY01(FunctionID:511001)
Setting items
Range
Unit
Contents
Default
Note
Commo
n
DPSY-NELD
0 - 99
-
Number of Event lock detect time
10
DPSY-TELD
1 - 99
s
Timer of detect event lock
10
DPSY-TELR
1 - 99
s
Timer of recovery from event lock
10
DPSY01-EN
Off / On
-
DPSY switch for DEV01
Off
DEV01
DPSY01-DEVNAME
[Preferred text]
-
item name of DPOSSY_Dev1
DPOS_SYN_Dev1
!
DPSY01-00NAME
[Preferred text]
-
state name of (0,0)state
Travelling0
!
DPSY01-01NAME
[Preferred text]
-
state name of (0,1)state
Off
!
DPSY01-10NAME
[Preferred text]
-
state name of (1,0)state
On
!
DPSY01-11NAME
[Preferred text]
-
state name of (1,1)state
Travelling1
!
DPSY01-UDFNAME
[Preferred text]
-
state name of undefined
Undefine
!
DPSY01-FLTNAME
[Preferred text]
-
state name of faulty
Faulty
!
DPSY01-DEVTYPE
1-Pole / 3-Pole
-
Device Type
1-Pole
DPSY01A-NOPSG
[Preferred signal]
-
Normally Open Signal of the single-pole or
phase A
Not Assigned
DPSY01A-NOPSGI
Off / On
-
Signal inverse or not
Off
DPSY01A-NCLSG
[Preferred signal]
-
Normally Close Signal of the single-pole or
phase A
Not Assigned
DPSY01A-NCLSGI
Off / On
-
Signal inverse or not
Off
DPSY01B-NOPSG
[Preferred signal]
-
Normally Open Signal of phase B
Not Assigned
DPSY01B-NOPSGI
Off / On
-
Signal inverse or not
Off
DPSY01B-NCLSG
[Preferred signal]
-
Normally Close Signal of phase B
Not Assigned
DPSY01B-NCLSGI
Off / On
-
Signal inverse or not
Off
DPSY01C-NOPSG
[Preferred signal]
-
Normally Open Signal of phase C
Not Assigned
DPSY01C-NOPSGI
Off / On
-
Signal inverse or not
Off
DPSY01C-NCLSG
[Preferred signal]
-
Normally Close Signal of phase C
Not Assigned
DPSY01C-NCLSGI
Off / On
-
Signal inverse or not
Off
DPSY01-OPC
And / Or
-
Normally Open contact grouping
And
DPSY01-CLC
And / Or
-
Normally Close contact grouping
Or
DPSY01-SPPEN
Off / On
-
Automatic event suppression function
Off
DPSY01-UDFEN
Off / On /
CHKONLY
-
undefined pallet check function
Off
DPSY01-UDFTIM
0.1 - 100.0
s
palette undefined check timer
30.0
DPSY01-FLTEN
Off / On /
CHKONLY
-
faulty pallet check function
Off
DPSY01-FLTTIM
0.1 - 100.0
s
palette faulty check timer
30.0
DPSY01-CTREN
Off / On
-
control mode (control enable)
Off
DPSY01-SYNEN
APPLY / Bypass
-
Synchronism Check Apply or Bypass
APPLY
DPSY01-CTRMENU
Off / On
-
control by MENU enable
Off
DPSY01-CTRAHMI
DIR / SBO
-
control action(Direct or SBO)by HMI
SBO
DPSY01-NSLBORD1
[Preferred signal]
-
select binary output read data(DataID)1 for no
direction command
5110018902011DC0
DPSY01-NSLBORD2
[Preferred signal]
-
select binary output read data(DataID)2 for no
direction command
5110018902011DC0
DPSY01-FSLBORD
[Preferred signal]
-
select binary output read data(DataID) for off
direction select command
5110018A02011DC4
DPSY01-OSLBORD
[Preferred signal]
-
select binary output read data(DataID) for on
direction select command
5110018602011DC6
DPSY01-FEXBORD
[Preferred signal]
-
execute binary output read data(DataID) for
off direction execute command
Not Assigned
DPSY01-OEXBORD
[Preferred signal]
-
execute binary output read data(DataID) for
on direction execute command
Not Assigned

Table of Contents

Related product manuals