Setting of AC analog input(Function ID: 200201)
Note: Channel numbers for rated settings are dependent on VCT type.
1A and 5A are shown above, but neglect them. They are invalid here. Confirm
that all have DEP setting from LCD menu or GR-TIEMS screen.
(iii) Example for VCT12B rated current change
Figure 5.2-7 shows the setting items and corresponding rating jumpers about VCT12B.
VCT jumper: Close or open the circuits named W* numbers corresponding to the
currents. The hatched areas are required to close or open.
For changing to 5A rated, insert jumpers at W6, 7, 8, 12, 13.
For changing to 1A rated, remove jumper at W6, 7, 8, 12, 13.