6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 391 -
Note: In the FL, user should verify the direction between the FL function and the other
protection function. For example, if Forward is set for the scheme switch [FL-Dir],
user should set Forward for the respective scheme switches [Z*S-DIR], [Z*G-DIR]
and [OC*-DIR]. If contradiction is found, the FL does not operate. For further
information, see section 2.32.6(iii).
Trigger signal for FL calculation
Figure 2.32-6 shows trigger signals for FL calculation. Result signals
1
from the respective
protection functions are summarized by logic OR, which provides the trigger signal.
1
Z1S DIR
Z1S
FL-DIR
310022EC63
FLZ_LocR
Z1S DIR
Reverse
Forward
Z1XS DIR
Reverse
Forward
Z2S DIR
Reverse
Forward
Z3S DIR
Reverse
Forward
Z1XS
Z2S
Z3S
1
1
OC1
OC1-Dir
Reverse
Forward
OC2-Dir
Reverse
Forward
OC2
1
1
Z1G
Z1G DIR
Reverse
Forward
Z1XG DIR
Reverse
Forward
Z2G DIR
Reverse
Forward
Z3G DIR
Reverse
Forward
Z1XG
Z2G
Z3G
1
1
1
Forward
Reverse
&
Forward
Reverse
Result signal of ZS function
Result signal of ZG function
Result signal of OC function
PLC signals
&
1
DIFL
RDIF
Result signal of DIF function
310022EC62
FLZ_LocF
310022EC66
FLAZ_LocF
1
Forward
Reverse
Trigger signal
for calculation
Trigger signal
for calculation
Figure 2.32-6 Calculation trigger from functions and PLC
1
Note: The result signals can start the FL calculation, but the result signals are not the same as the
operation signals of
Figure 2.32-5.