6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1596 -
(PIXIT Ed.1&Ed.2)
14. PIXIT FOR CONTROL MODEL(Continued)
ID
Ed
Description
Value / Clarification
Ct12
1,2
How to force a test-not-ok” respond with
Operate request
DOns, SBOns, DOes:
[Example1]
Set orCat as unsupported value
-> Cause AddCause as “Not-
supported(1)”
[Example2]
Set ctlCat same as stVal
-> Cause AddCause as “Position-
reached(5)”
SBOes: (Only Ed1)
Same as above. Or,
[Example3]
Set Oper parameters as different
parameter from the parameter of
SelectWithVal
-> Cause AddCause as “Parameter-
change-in-execution (6)”
Ct13
1,2
Which origin categories are supported /
accepted
N bay-control
Y station-control
Y remote-control
N automatic-bay
Y
automatic-station
Y automatic-remote
N maintenance
N process
maintenance (7): N
process (8): N
Ct14
1,2
What happens if the orCat value is not
supported or invalid
DOns, SBOns, DOes, SBOes:
“test-not-ok” IED respond
Ct15
1,2
Does the IED accept a SelectWithValue /
Operate with the same control value as the
current status value
Is this behavior configurable
DOns, SBOns, DOes, SBOes: N
Fixed
Ct16
1,2
Does the IED accept a select/operate on the
same control object from 2 different clients at
the same time
DOns: N
SBOns: N
DOes: N
SBOes: N
Note:
Commands are refused until
the new position is not reached
or a timeout does not occur.