6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 658 -
Operate-Off command check
Similarly, the point “BO3-RB must be applied for the setting [SPOS01-FEXBORD].
Operate logic in
SPOS01
&
Signal designated by
setting [SPOS01-FEXBORD]
BO3 circuit at
IO_#1
Contact health check
logic in SPOS01
Result of contact
health check
SPOS01_FEX_BO
510001_8101011DD0
BO3-RB
200B01_8102021113
Connection made by the user
Figure 4.1-36 Example connection of “Operate command off” for the health check feature
Proper setting for the contact health check (normal setting, example #1)
Figure 4.1-37 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1, BO2 and BO3 contacts. To check that the contact health check function is
working correctly, the respective points of the BO-RBs should be connected as shown in Table
4.1-22, to demonstrate that the settings are physically matched with the BO contacts.
Table 4.1-22 Setting example for contact health check
Example #1
Health check setting for Example #1
“SPOS01_SL_BO_FLG is connected to BO1 at IO#1
200B01 8002001113(BO1-RB) set for [SPOS01-SLBORD]
OK
“SPOS01_OEX_BO_CSF” is connected to BO2 at IO#1
200B01 8102011113(BO2-RB) set for [SPOS01-OEXBORD]
OK
“SPOS01_FEX_BO_CSF” is connected to BO3 at IO#1
200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD]
OK
Plus (+)
SW 3
SPOS01_SL_BO_FLG
(510001_8501011F76)
SW1 driven with
BO1 at IO_SLOT1
BO1
Drivers
Select
command ON/OFF
BO1-RB
(200B01_8002001113)
BO2
Operate-On
command
SPOS01_OEX_BO
(510001_8201011DD3)
BO2-RB
(200B01_8102011113)
BO3
Operate-Off
command
SPOS01_FEX_BO
(510001_8101011DD0)
BO3-RB
(200B01_8202021113)
SW2 driven with
BO2 at IO_SLOT1
SW3 driven with
BO3 at IO_SLOT1
Remote/Local-end
SW 2
SW 1
Minus ()
BIO module
43SW
On
Command
Off
Command
Figure 4.1-37 Contact health check setting and 43SW scheme for example #1
Setting for erroneous contact health check (improper setting, example #2)