EasyManua.ls Logo

Toshiba GR200 Series - (iii) BO connection for “Operate command On;Off”; (iv) Contact health check

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 891 -
DPOS01_OSL_BO_FLG” and DPOS01_FSL_BO_FLG.
(iii) BO connection for Operate command On/Off
Figure 4.8-44 exemplifies the connection for operate command On/Off. Suppose that connection
with the BOs is achieved by the PLC function using connection points DPOS01_OEX_BO and
DPOS01_FEX_BO; as a result, the “Operate command On and the Operate command Off
signals are issued at BO3 and BO4 respectively.
BO3_SOURCE
200B01 310202E11D
DPOS01_OEX_BO
(512001 8203011DD3)
Operate logic in DPOS01
PLC connection point in BO3
Operate logic for
Operate command
On
≥1
&
[BO3_CPL]
Off
On
&
DRIVER
BO3
Signal captured by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
Operate
command
On to the
device
≥1
BO3
(200B01_8202021112)
BO3-RB
(200B01_8202021113)
BO3 and BO4 circuit at IO#1 (Function ID: 200B01)
Terminal and
wire
To contact health
check
BO4_SOURCE
200B01 310203E11D
DPOS01_FEX_BO
(512001 8103011DD0)
PLC connection point in BO4
Operate logic for
Operate command
Off
≥1
&
[BO4_CPL]
Off
On
&
DRIVER
BO4
Signal captured by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
≥1
BO4
(200B01_8302031112)
BO4-RB
(200B01_8302031113)
To contact health
check
To contact health
check
To contact health
check
Connected by
Programming
Connected by
Programming
Operate
command
Off to the
device
Figure 4.8-44 Example of operate commands connected with BO3 and BO4 at IO#1
Note: Table 4.8-18 shows the remaining signals with the exception of
DPOS01_OEX_BO” and DPOS01_FEX_BO”.
(iv) Contact health check
The DPOS01 function has a contact health check feature for the BO circuits; hence, the user
is able to connect an output signal to the contact health check function when Fixedlogic is set
for scheme switch [DPOS01-LGXFEOT]. Consequently, the DPOS01 function can determine
whether the signal has been successfully output from the BO. If a failure is reported, the
DPOS01 function determines that the signal has not been output successfully to the BO; then,
the command On or Off is canceled immediately and the DPOS01 function returns to the Wait
for a command stage.
Note: Table 4.8-34 shows settings for the health check feature in the other DPOS
functions.

Table of Contents

Related product manuals