6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 721 -
Settings for extra contact health check (special setting, example #3)
Figure 4.2-51 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point DPSY01_OSL_BO_FLG is actually chosen for the
setting [DPSY01-OSLBORD]; i.e. BO1-RB is not chosen for this selection. This special example
can issue a select command, which is called operated by internal select function. The user
does not need to consider the use of a BO circuit for a select command, when there are no BO
circuits available.
Table 4.2-33 Extra setting example for contact health check
Example #3
Setting for example #3
“DPSY01_OSL_BO_FLG” is not connected to any BO
[DPSY01-OSLBORD] =” DPSY01_OSL_BO_FLG”
OK
“DPSY01_FSL_BO_FLG” is not connected to any BO
[DPSY01-FSLBORD]=” ” DPSY01_OSL_BO_FLG”
OK
“DPSY01_OEX_BO_CSF” is connected to “BO3” at IO#1
[DPSY01-OEXBORD]=” 200B018202021113” (BO3-RB)
OK
“DPSY01_FEX_BO_CSF” is connected to “BO4” at IO#1
[DPSY01-OEXBORD]=” 200B018202031113” (BO4-RB)
OK
Plus (+)
Drivers
BO3
BO4-RB
(200B01_8302031113)
BO4
BO3-RB
(200B01_8202021113)
SW4 is driven with
BO4 at IO#1
Local/Remote-end
SW 3
SW 1
Minus ()
BIO module
43SW
SW 2
SW 4
SW3 is driven with
BO3 at IO#1
SW1 is not driven with
any BO
SW2 is not driven with
any BO
Physical BOs
are virtualized.
DPSY01_OSL_BO_FLG
(511001 8602011DC6)
Select command
Closing
Operate command
Closing
DPSY01_OEX_BO
(511001 8202011DD3)
Operate command
Open
DPSY01_FEX_BO
(511001 8102011DD0)
Closing
command
Select command
Open
DPSY01_FSL_BO_FLG
(511001 8A02011DC4)
Open
command
Figure 4.2-51 Contact health check setting and 43SW diagram for example #3
Table 4.2-34 PLC monitoring points (Output signal for event suppression function in DPSY)
Signal Number
Signal Name
Description
511001 3102011001
DPSY01_3PH_STATE
DPSY01 3ph_state
511001 3102021001
DPSY02_3PH_STATE
DPSY02 3ph_state
511001 8102011F5F
DPSY01_F_QLT_SPP
Event suppression detected (DPSY01)
511001 8102021F5F
DPSY02_F_QLT_SPP
Event suppression detected (DPSY02)
Table 4.2-35 PLC monitoring points (Output of select signal in DPSY)
Signal Number
Signal Name
Description
511001 8602011DC6
DPSY01_OSL_BO_FLG
DPSY01 select (CLOSE) command for Binary Output.
511001 8602021DC6
DPSY02_OSL_BO_FLG
DPSY02 select (CLOSE) command for Binary Output.
511001 8A02011DC4
DPSY01_FSL_BO_FLG
DPSY01 select (OPEN) command for Binary Output.
511001 8A02021DC4
DPSY02_FSL_BO_FLG
DPSY02 select (OPEN) command for Binary Output.