Toshiba GR200 Series - (i)-2 Defining DIR mode; (ii) Mapping output data

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 724 -
SBOw
Oper
Cancel
origin
stSeld
sboClass (choice operate-once)
ctlmodel (choiceSBOes or SBOns)
sboClass can be found by scrolling down.
Figure 4.2-53 LN editing screen for SBO mode
Defining DIR mode
Figure 4.2-54 exemplifies the SPOS logic node saved as CSWI1”. In the DIR mode, the
following three items should be selected using GR-TIEMS.
Oper
origin
ctlmodel (choice DOes or DOns )
Figure 4.2-54 LN editing screen for DIR mode
(ii) Mapping output data
The user should group the DPSY01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS. Figure 4.2-55 illustrates
how to map a signal; it indicates that the signals for the DPSY01 function are required to be
mapped for IEC 61850 communications.