4.1.3 Operate logic for SBO/DIR modes
Once the operation of the select logic is completed, the operate logic start to control the device.
(i) Receiving “operate command On” from the remote- end
Figure 4.1-19 depicts the reception of the operate command On from the remote- end.
Signal reception in
IEC61850
On control from remote-end
Do nothing
Operation
decision
Success
Failed
Operate logic
Wait for a command
Signal output
On control from front-panel
Off control from front-panel
Off control from remote-end
On control by PLC function
Off control by PLC function
Wait for a next command
Select logics
Select command Off from remote-end
Select command On from remote-end
Select command Off from front panel
Select command On from front panel
Select command On by the PLC
function
Select command Off by the PLC
function
Figure 4.1-19 Outline of operate command forOn
Mapping required for Input point
Figure 4.1-20 illustrates the operate logic when an Operate command On (Remote-ON-
Control)” signal is applied to the SPOS01 function. The input-point “DEV01_CONTROL_REQ”
is used for the reception of the Operate command On (Remote-On-Control)”.