- 1589 -
(PIXIT Ed.1&Ed.2)
9. PIXIT for Reporting model (continued)
What is the buffer size for each BRCB or how
many reports can be buffered
For example, LLN0$ST$Health
can be stored 408 events.
Pre-configured RCB attributes that are
dynamic, compare SCL report settings
May the reported data set contain:
- structured data objects
- data attributes
What is the scan cycle for binary events
Is this fixed, configurable
More than 1.6 milliseconds
Configurable
Does the device support to pre-assign a RCB to a
specific client in the SCL
After restart of the server is the value of ConfRev
restored from the original configuration or
retained prior to restart
Restored from original
configuration
Does the server accepts any client to
configure/enable a BRCB with ResvTms=‐1?
What fields are used to do the identification?
N
AP‐Title N
AE‐Qualifier N
<other field> N
When BRCB.ResvTms is exposed, what is
default value for BRCB.ResvTms if client does
not write (must be > 0)
Or
When BRCB.ResvTms is not exposed, what is
the internal reservation time (must be >= 0)
Is it supported to change LLN0.Mod online?
10. PIXIT FOR LOGGING MODEL
Not applicable