RS485 communication
When the IED has an RS485 module for the communication, the user can select and set its
transmission and error check parity codes. Figure 11.6-1 shows the setting screen when the
RS485 module (#1) operates.
RS485
10:48 1/2
RS485_1_BRATE_SW +
19.2kbps
RS485_1_BRATE_SW +
NONE
Figure 11.6-1 RS485 setting menu (on IED screen)
Setting of RS485 (Function ID: 232201)
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
Module
#1
RS485_1_BRATE_SW
9.6 / 19.2 / 38.4 /57.6 / 115.2
kbps
Transmission speed
19.2
RS485_1_PAR_SW
NONE / ODD /EVEN
Parity check code