EasyManua.ls Logo

Toshiba GR200 Series - (vi) Receiving “Operate command Off” using PLC function; (vi)-1 Input signal from the PLC function; (vi)-2 Output signal to BO

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 874 -
to [DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.
††
Note: To identify the input and output signal-points in the other DPOS logics, see Table
4.8-14 for PLC#1, Table 4.8-15 for PLC#2, Table 4.8-18 and Table 4.8-20 for output
signals.
‡‡
Note: The “Operate failed” signal is issued when a state-change remains undetected
following expiration of the setting to timer [DPOS01-RST].
(vi) Receiving “Operate command Off” using PLC function
Figure 4.8-29 outlines the reception of the operate command Off by the PLC function.
Wait for a command
Operate command Off from the local-end
Operate command Off from the remote-end
Operate command On by the PLC
Wait for a next command
Select stage
Select command Off from the remote-end
Select command On from the remote-end
Select command Off from the local-end
Select command On from the local-end
Select command On by the PLC
Select command Off by the PLC
Operate command On from the remote-end
Operate command On from the local-end
PLC logic programmed
by the user l
Operate command Off by the PLC
Do nothing
Operation
decision
Success
Failed
Operate logic
Signal output
Figure 4.8-29 Outline of Operate command ‘Off’
Input signal from the PLC function
Figure 4.8-30 depicts the operate logic when an Operate command Off (PLC-Off-control)”
signal is generated by the PLC function. There are two input points for reception of this
command signal, like the signal “Operate command On (PLC-On-control)”, That is, if an
interlock check is required, apply the signal at connection point (PLC#3: i.e.
DEV01_OP_INTERLOCK). If, on the other hand an interlock check is not required, apply the
signal at the other connection point (PLC#4: i.e. DEV01_OP_COMMAND). PLC#3 and PLC#4
are denoted as PLC#1 and PLC#2 in Table 4.8-3.
Output signal to BO
The DPOS01 function, in Figure 4.8-30, can issue an Operate” signal at output-point
DPOS01_FEX_BO”, when the DPOS01 function determines that the signal “PLC-Off-Control”
is true.

Table of Contents

Related product manuals