- 873 -
is true.
DPOS01 function (Function ID: 512001)
Operate Cmd.
with ILK† condition
Operate Cmd.
without ILK† condition
Command “PLC-On-Control” requiring ILK† check
(PLC#3 connection point)
ILK† condition (“ON”) passed
User configurable condition
(PLC#1 connection point)
“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
“DPOS01_OEX_BO” §§
(512001 8203011DD3)
“DPOS01_OEC_OK_CS”
(512001 8103011E82)
ASEQ function§” is in progress
“DPOS01_EX_FFL”
††
(512001 8603011E91)
Detection of state-change in a device
User configurable condition
(PLC#2 connection point)
“DPOS01_EX_CMP”
(512001 8003011E93)
Command “PLC-On-Control” not requiring ILK† check
(PLC#4 connection point)
Figure 4.8-28 Operate On by the PLC function in DPOS01
††
†Note: The ILK function can provide the operation criteria for “On”.
‡Note: An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative “operate-condition” programmed by the user is required in place of
the signal generated by the original operate-condition logic, connect the
alternative “operate-condition” to the logic shown in Figure 4.8-28 using
connection point #1 “User configurable condition”. That is set the scheme switch
[DPOS01-LGCTRCON] to PLC and use “DPOS01IN_TMP_35”.
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for scheme
switch [DPOS01-LGCFEXOT]. If the signal is to be issued from the logic
programmed by the user instead of the logic shown in Figure 4.8-20, connect the
“Operate completed” signal generated in the user-programmed logic to connection
point #2 “User configurable condition”. That is, set the scheme switch [DPOS01-
LGCFEXOT] to PLC and use “DPOS01IN_TMP_42”.
*Note: The user can select a type of output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting applied