6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 873 -
is true.
DPOS01 function (Function ID: 512001)
Assign to BOs
Operate Cmd.
with ILK condition
S
R
0.1 50.0 s
[DPOS01-CPW]
Operate Cmd.
without ILK condition
Operate condition
[DPOS01-LGCTRCON]
Fixedlogic
Fixedlogic
[DPOS01-LGCFEXOT]
Command PLC-On-Control requiring ILK check
(PLC#3 connection point)
ILK condition (“ON”) passed
DPOS01-Close
DPOS01IN_TMP_35
512001 810301EE57
User configurable condition
(PLC#1 connection point)
DPOS01_OEC_OK_CSF
(512001 8003011E7F)
&
&
1
&
1
1
&
&
&
DPOS01_OEX_BO §§
(512001 8203011DD3)
Input
Output
Operate logic in DPOS01
To BO connection
DPOS01_OEC_OK_CS
(512001 8103011E82)
[DPOS01-PLSM]*
Fix
Var
Operate Failed
[DPOS01-RST]
ASEQ function§ is in progress
ASEQ_MULTI_SEL
DPOS01_OEC_OK_CSF
DPOS01_EX_FFL
††
(512001 8603011E91)
To Wait for a command
&
Detection of state-change in a device
&
DPOS01IN_TMP_42
512001 820301EE5E
User configurable condition
(PLC#2 connection point)
1
&
DPOS01_EX_CMP
(512001 8003011E93)
Operate Completed
1.0s- 100.0s
0
t
DEV01_CL_INTERLOCK
512001 800301EE33
Command PLC-On-Control not requiring ILK check
(PLC#4 connection point)
DEV01_CL_COMMAND
512001 800301EE32
Figure 4.8-28 Operate On by the PLC function in DPOS01
††
Note: The ILK function can provide the operation criteria for “On”.
Note: An “operate condition signal is generated in the operate-condition logic (see
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative “operate-condition” programmed by the user is required in place of
the signal generated by the original operate-condition logic, connect the
alternative “operate-condition” to the logic shown in Figure 4.8-28 using
connection point #1 “User configurable condition. That is set the scheme switch
[DPOS01-LGCTRCON] to PLC and use “DPOS01IN_TMP_35.
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for scheme
switch [DPOS01-LGCFEXOT]. If the signal is to be issued from the logic
programmed by the user instead of the logic shown in Figure 4.8-20, connect the
“Operate completed” signal generated in the user-programmed logic to connection
point #2 “User configurable condition”. That is, set the scheme switch [DPOS01-
LGCFEXOT] to PLC and use “DPOS01IN_TMP_42”.
*Note: The user can select a type of output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting applied