4.9.2 Cancel logic for SBO mode
In the SBO control mode, the reception of a cancel command can be possible when the cancel
conditions are satisfied, the function can discard the select command; finally, the operation
returns to the initial stage (i.e., “wait for a command”).
(i) Receiving “Cancel” from the remote-end
Figure 4.9-21 depicts the cancel command procedure for a cancel command initiated from the
remote-end.
Signal reception in
IEC61850
Cancel from remote-end
Do nothing
Cancel
decision
Success
Failed
Cancel logic
P2 control from the remote-end
P3 control from the remote-end
P1 control from the local-end
P2 control from the local-end
P1 control by the PLC function
P3 control from the local-end
P2 control by the PLC function
Wait for a command
Operate logic
Operate command
Operate logic
P1 control from the remote-end
P3 control by the PLC function
Select stage
Cancel from the local-end
Wait for a next command
Figure 4.9-21 Outline of ‘cancel command from remote-end
Input point required mapping
Figure 4.9-22 depicts the cancel logic when a Cancel command (Remote-Cancel) signal is
applied to the TPOS01 function. The input-point “DEV01_CONTROL_REQ” is the same as
that for the Selection command P1 (Remote-P1-Control)signal.
TPOS01 function (Function ID: 513001)
TPOS01_ CC_SS
(513001_8604011E95)
DEV01_CONTROL_REQ
Cancel command
Command Remote-cancel
513001_7004016D08
510001 7001016D08
Input
Output
Cancel logic in TPOS01
Cancel condition
&
&
Successes to cancel
Operation Failed
TPOS01_CC_FS
(513001_8704011E96)
Do nothing
To Wait for a command
Figure 4.9-22 ‘Cancel’ from the remote-end in TPOS01
Note: The logic cancel condition” is shown in Figure 4.9-25.