EasyManua.ls Logo

Toshiba GR200 Series - 4.1.4 Setup for BIO module; (i) BI connection for status-signals; (i)-1 Connection with Binary input circuit

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 654 -
4.1.4 Setup for BIO module
The user should connect the SPOS input/output points with the BI and the BO circuits;
subsequently, the SPOS function is able to issue select and operate commands. The user should
execute the following four steps below.
i BI connection for status-signals
ii BO connection for “Select command On/Off”
iii BO connection for operate command
iv Contact health check
Note that the SPOS01 function commences operation when the scheme switch [SPOS01-EN]
is set to On.
(i) BI connection for status-signals
Figure 4.1-30 exemplifies the reception of signals at the SPOS01 function; the user can set a
input-point using the setting [SPOS01-NOPSG].
Note: Normally an input-signal corresponding to phase-A is generated using a normally-
open contact (NO). If the signal is generated by the normally-closed contact, the
user is required to set scheme switch [SPOS01-NSOSGI] On in order that the
input-signal should be decided in inversion.
Connection with Binary input circuit
Suppose an input signal is provided on the first BI circuit at IO#1 slot. In this case, the user
should set the input point (200B01 8001001110) for the setting [SPOS01-NOPSG], otherwise,
the SPOS01 function cannot run correctly.
Signals by Binary input circuits
Output
Signal acquisition logic in SPOS01
SPOS01_F_QLT_SPP
(510001_8101011F59)
Event suppression detector
Chattering detector
Status before chattering
S
R
BI signal connected by
setting [SPOS01-NOPSG]
[SPOS01-EN]
On
[SPOS01-SPPEN]
On
&
&
&
SPOS01_STATE
(510001_0001011001)
1
To select and operate
condition logics
Figure 4.1-30 Acquisition of binary input signal in SPOS01
Note: The user should set the actual input-points. For Input points see in Chapter
Technical description: Binary IO module
.
‡Note: In Figure 4.1-30 two signals can be issued: SPOS01_STATE and
SPOS01_F_QLT_SPP. One is used in the select condition logic and the operate
condition logic (see Figure 4.1-13 and Figure 4.1-29). Another is used for operation

Table of Contents

Related product manuals