10.5.8 Error terminal configuration (Term ID)
The user can monitor the network configuration between terminals. The error signal is issued
when the erroneous configuration is observed for ten seconds. For monitoring, the user should
set Off for the settings [MSCHK-EN] and set On for the [CHK_TERM_CNF:Sw]. For more
information about the master-slave relationship, see chapter
Relay application:
Communication application
.
(i) Error level
Generally, the default error level is set at level 2 (Serious error (Comm)), but the user can
program the level using setting [CHK_TERM_CNF:Lvl]; then, set On for the setting
[CHK_TERM_CNF:Sw]. The manufacturer sets ten (10) seconds to detect the failure; it is reset
with in a second when the failure is cleared.
(ii) Error message
When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-17 Error messages provided by the supervisor in CHK_TERM_CNF
Message and level
Meaning of the information
Term ID error
Detection for error ID in the network configuration
Error level
Serious error (Level 2)
Table 10.5-18 Detailed information in Hexadecimal in CHK_TERM_CNF
Display area
Meaning of the detailed information
N/A
(No information is displayed)