- 182 -
2.11.2 Scheme logic
Figure 2.11-1shows the DTT scheme logics. For the reception of a pair of trip signals from a
remote terminal, the logic has two PLC connection points ‘R1.DTT1’ and ‘R1.DTT2’. The user should
connect a remote trip signal provided by the communication with the PLC connection points using
PLC function.
Blocking the DTT1 function is also available when an external signal is injected to the
logic using PLC connection point “DTT1_BLOCK”. Incidentally, the user can program to
operate the DTT1 function with the absence of the delaying [TDD1] using PLC connection point
“DTT1_INST_OP”. The user should notice that issuing for the TRC function is just designed
for the three-phase tripping command.
Figure 2.11-1 DTT1 and DTT2 scheme logics