EasyManua.ls Logo

Toshiba GR200 Series - 2.13.6 Setting

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 213 -
2.13.6 Setting
DEFCAR (Function ID: 437001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Carrier_DEF
DEF-CAR
Off/POP/UOP/BOP
DISCAR scheme enable
Off
DEF-ECHO
Off / On
-
Echo function enable
Off
DEF-WKIT
Off / On
-
Weak infeed trip function enable
Off
DEFCAR-CHSEL
Single / And / Guard
-
Carrier channel configuration
Single
TDEFCF
0.00 - 0.30
s
DEF carrier trip delay time
0.15
TDEFCB
0.00 - 0.30
s
DEF carrier trip delay time
0.15
TDEFC
0.00 - 0.30
s
DEF carrier trip delay time
0.00
TREBK-DEF
0.00 - 10.00
s
Current reverse blocking time
0.10
TCHD-DEF
0.000 - 0.100
s
Coordination timer in BOP function
0.012
TSBCT-DEF
0.00 - 1.00
s
SBCNT timer
0.10
Output
DEFCAR-TPMD
1P / 3P
-
DEF carrier trip mode, phase segregated trip or 3-
phase trip
3P
DEFCAR-ARCBlk
Non / Block
-
Autoreclose block by DEF carrier trip
Block

Table of Contents