- 484 -
(i) Setting example 1 (Bus-bar VT=three phases, Line VT=phase-A)
a. Phasor diagram in Line
b. Phasor diagram in Bus-bar
Figure 2.35-6 Example 1: Input voltages and respective phasor diagram for SYN1
1
Note: The structure of VCT is dependent on the VCT type. (See chapter
Technical
description: Transformer module
)
2
Note: V
Bus-bar
is Running voltage.
3
Note: V
Line
is Incoming voltage.
Figure 2.35-6 shows the VCT input voltages and phases from Bus-bar and Line, and
shows the phase relationship between the running voltage and the incoming voltage. In this
case, configure the settings in accordance with Figure 2.35-6 and Table 2.35-7.
Table 2.35-7 Setting for example 1
Bus-bar VT= Three phase
Line VT= Phase-A
Running voltage (V
a
)= Phase-A (Bus-bar VT)
Incoming voltage (Vs)= Phase-A (Line VT)
[SYN-VBus] = V-L1
[SYN-VLine]= V3
4
Note: Set V3 for the scheme switch [SYN-VLine]. This is because V3 and V-L1 are in the
same phase.