EasyManua.ls Logo

Toshiba GR200 Series - 4.6.6 Voltage selection for line arrangement; (i) Setting example

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 816 -
4.6.6 Voltage selection for line arrangement
As shown in Figure 4.6-16, input-voltage signals are required in response to the line and bus-
bar arrangement. Incidentally, the input-voltage signals supplied by the VTs are applied to the
IED via the transformer module (VCT); hence, the input-voltage signal should correspond
with the required relay-element. On this account, settings are provided in the SYNCHK_Ry
function.
Va V-L1
Vb V-L2
Vc V-L3
Signal
nam es
Vs V3
Vs2 V4
SYNCHK_ Ry1
Relays for
running voltage
Relays for
incoming voltage
Schem e switches [SyncRy1-VR] etc. select a running
voltage and an incom ing voltage.
SYNCHK_ Ry2
Schem e switches [SyncRy2-VR] etc. select a running
voltage and an incom ing voltage.
Relays for
incoming voltage
Relays for
running voltage
V2a V2-L1
V2b V2-L2
V2c V2-L3
VCT
Setting
nam es
Figure 4.6-18 Voltage signals selected using scheme switches
Note: For the actual terminal arrangement and signals injected, see chapter
Technical
description: Transformer module for AC analog input.
Figure 4.6-18 illustrates that the signals injected are distributed using scheme switches:
[SyncRy1-VR], [SyncRy1-VI], [SyncRy1-VR], and [SyncRy1-VI]. Examples below show how to
apply a voltage signal for the required relay-element.
(i) Setting example
Figure 4.6-19 depicts an example of a busbar arrangement and S43P logic programmed by the
user. In this case, only the SYNCHK_Ry1 function is used; therefore, the user need only select
the signal provided by the S43P logic for the SYNCHK_Ry1 function.

Table of Contents

Related product manuals