- 816 - 
 
4.6.6  Voltage selection for line arrangement 
As shown in Figure 4.6-16, input-voltage signals are required in response to the line and bus-
bar arrangement. Incidentally, the input-voltage signals supplied by the VTs are applied to the 
IED via the transformer module (VCT†); hence, the input-voltage signal should correspond 
with the required relay-element. On this account, settings are provided in the SYNCHK_Ry 
function. 
Relays for 
running voltage 
Relays for 
incoming voltage 
Schem e switches [SyncRy1-VR] etc. select a running 
voltage and an incom ing voltage. 
Schem e switches [SyncRy2-VR] etc. select a running 
voltage and an incom ing voltage. 
Relays for 
incoming voltage 
Relays for 
running voltage 
 
Figure 4.6-18 Voltage signals selected using scheme switches 
†Note: For the actual terminal arrangement and signals injected, see chapter 
Technical 
description: Transformer module for AC analog input.
 
 
Figure 4.6-18 illustrates that the signals injected are distributed using scheme switches: 
[SyncRy1-VR], [SyncRy1-VI], [SyncRy1-VR], and [SyncRy1-VI]. Examples below show how to 
apply a voltage signal for the required relay-element. 
 
(i)  Setting example 
Figure 4.6-19 depicts an example of a busbar arrangement and S43P logic programmed by the 
user. In this case, only the SYNCHK_Ry1 function is used; therefore, the user need only select 
the signal provided by the S43P logic for the SYNCHK_Ry1 function.