6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 815 -
SYNCHK_Ry (Function ID: 561001)
SYNC01_RY1_USE_STS
560001 800B01EDED
PLC signals for relay selection relating to SYNCHK1
SYNC01_RY2_USE_STS
560001 800B01EDEE
SYNCHK_Ry2
&
SYNCHK_Ry1
SyncRy1-Ɵ≈0
SyncRy1-
SyncRy1-dV
SyncRy1-df
SyncRy1-Ɵ less
ΔƟ1 less
ΔƟ1
ΔƟ1≈0
Δf1
ΔV1
&
&
&
&
&
SyncRy2-Ɵ≈0
SyncRy2-
SyncRy2-dV
SyncRy2-df
SyncRy2-Ɵ less
ΔƟ2 less
ΔƟ2
ΔƟ2≈0
Δf2
ΔV2
&
&
&
&
SYNCHK_Ry (Function ID: 561001)
SYNCHK1
(Function ID: 560001)
&
&
&
&
&
&
&
&
&
&
SYNC02_RY1_USE_STS
560001 800B02EDED
PLC signals for relay selection relating to SYNCHK2
SYNC02_RY2_USE_STS
560001 800B02EDEE
SYNCHK2
(Function ID: 560001)
SYNC02_SYN_CLC
Sync success
To DPSY02
560001 850B021F59
SYNC01_SYN_CLC
Sync success
To DPSY01
560001 850B011F59
Selection signals are
injected by PLC logic made
by the user.
Figure 4.6-17 Relay selection made using PLC signals
Table 4.6-7 PLC connection point (Relay selection)
Signal Number
Signal Name
Description
M/O
560001 800B01EDED
SYNC01_RY1_USE_STS
SYNCHK1 use SYNCHK_RY1
M
560001 800B01EDEE
SYNC01_RY2_USE_STS
SYNCHK1 use SYNCHK_RY2
M
560001 800B02EDED
SYNC02_RY1_USE_STS
SYNCHK2 use SYNCHK_RY1
M
560001 800B02EDEE
SYNC02_RY2_USE_STS
SYNCHK2 use SYNCHK_RY2
M