EasyManua.ls Logo

Toshiba GR200 Series - 5.3.2 Configuration switch

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1040 -
5.3.2 Configuration switch
The CPU module has a jumper to change configuration mode (Jumper W6). Figure 5.3-3 shows
the location. For default mode (normal), Pins 1-2 and 3-4 are open (i.e., default configuration
has been set by the manufacture in accordance with the order code). When the user wishes to
alter the other mode particularly, close either Pin 1-2 or Pin 3-4 using a jumper (Optional EP-
221).
COM#2
CPM2
COM#1
CPU
COM#3
COM#4
COM#5
W5
2-1
4-3
W8
2-1
4-3
W6
(1-2)
W6
(3-4)
Jumper
Configuration mode
Open
Open
Default (normal) mode(i.e.,
manufacture setting mode )
Closed
Open
Constrained mode (1A rated)
Open
Closed
Constrained mode (5A rated)
CPU
2-1
4-3
2-1
4-3
2-1
4-3
W6
2-1
4-3
W7
2-1
4-3
Figure 5.3-3 Configuration switch
Note: Alter the configuration mode before VCT setting. Using GR-TIEMS, the user
needs to rewrite the settings. See
Chapter Installation and setting: Changing
rated current
for more detail.

Table of Contents