6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 742 -
SOFTSW1 function (Function ID: 522001)
S4301_CHG_TO_ON
522001 850A04EDE1
510001 7001016D08
Signals from user-PLC logic
Output
Select logic in SOFTSW1
0.1s
0
t
0.6s
0
t
&
Select condition
ON-control command
(PLC connection point #1)
Operate command
For DIR operation
“S4301_OSD_CSF
(522001_8F0A411F49)
Select Failed
For monitoring
Select success
To Wait for a command
Figure 4.3-10 Select logic for ON operation by PLC in SOFTSW1
††
Note: Direct operation mode (DIR) is only available.
Note: select condition signal is provided. See Figure 4.3-12.
††
Note: To identify the input and output points of the other SOFTSW logics, see Table
4.3-3 and Table 4.3-9.
Output signal for monitoring
The SOFTSW1 function shown in Figure 4.3-10, can issue a “Select success” signal at output-
point “S4301_OSD_CSF”.
Note: The signal “S4301_OSD_CSF” is the same as the signal shown in Figure 4.3-6.
(vi) Receiving “Select command for Off operation” using PLC function
Input signal required to connect
Figure 4.3-11 shows the SOFTSW1 logic for a “Select command (PLC-OFF-Control)” signal.
The input signal is generated using the user-programmed PLC logic; the user can connect the
signal for the PLC connection point S4301_CHG_TO_OFF.
SOFTSW1 function (Function ID: 522001)
S4301_CHG_TO_OFF
522001 860A04EDE0
510001 7001016D08
Signals from user-PLC logic
Output
Selection logic in SOFTSW1
0.1s
0
t
0.6s
0
t
&
Select condition
OFF-control command
(PLC connection point #2)
Operate command
For DIR operation
“S4301_FSD_CSF
(522001_8D0A411F45)
Select Failed
For monitoring
Select success
To Wait for a command
Figure 4.3-11 Select logic for OFF operation by PLC in SOFTSW1
††
Note: Direct operation mode (DIR) is available only.
Note: Signal select condition is provided. See Figure 4.3-12.
††
Note: To identify the input and output points of the other SOFTSW logics, see Table
4.3-4 and Table 4.3-9.