- 1197 -
Statistics data (Demand value group)
The user can keep track of the variable power quantities using the demand feature; the
statistical information (such as maximum load, minimum load, and averaged load) are
collected in every defined period.
Table 9.4-1 Demand data for ’33 and 37’ software
3
Current in phase-a (Max., Min., and Averaged data)
Current in phase-b (Max., Min., and Averaged data)
Current in phase-c (Max., Min., and Averaged data)
Residual current (Max., Min., and Averaged data)
I
e
Max, I
e
Min, I
e
Ave
(1)
The other residual current on parallel lines (Max., Min., and Averaged)
I
em
Max, I
em
Min, I
em
Ave
(1)
Voltage applied at phase-a (Max., Min., and Averaged data)
Voltage applied at phase-b (Max., Min., and Averaged data)
Voltage applied at phase-c (Max., Min., and Averaged data)
Voltage applied between phases-a-to-b (Max., Min., and Averaged data)
V
ab
Max, V
ab
Min, V
ab
Ave
Voltage applied between phases-b-to-b (Max., Min., and Averaged data)
V
bc
Max, V
bc
Min, V
bc
Ave
Voltage applied between phases-c-to-a (Max., Min., and Averaged data)
V
ca
Max, V
ca
Min, V
ca
Ave
Zero-sequence voltage (Max., Min., and Averaged data)
V
0
Max, V
0
Min, V
0
Ave
(2)
Reference voltages (Max., Min., and Averaged data)
The other reference voltages (Max., Min., and Averaged data)
V
s2
Max, V
s2
Min, V
s2
Ave
9.4.1 Demand information on the screen
The statistics feature can provides the information about maximum, minimum, and averaged
values. Figure 9.4-1 shows the example about the current information
Figure 9.4-1 Example of Demand Value screen
9.4.2 Max/Min/Averaged information about the demand feature
The demand feature is used to calculate the active power (P), the reactive power (P), and the
complex power (S) that are weighted with the plus (+) or minus (–) sign; the calculation will be
Demand Value
10:48 1/42
Ia Max
0.00kA
Ia Min
0.00kA
Ia Ave
0.00kA