Toshiba GR200 Series - (iii)-2 OR interlock operator

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 830 -
used for Quality can be found immediately below Table 4.7-3.
stVal
Quality
stVal
Quality
AND ( )
Output
Input(A)
Input(B)
stVal
Quality
Figure 4.7-5 Logic of interlock operator (AND) and Input/Output signals
OR interlock operator
When quality information (Quality) is applied to the interlock operator OR, the quality
information is affected by device status (stVal). Table 4.7-5 shows two-input-signals (A, B) and
the output signal for OR
Table 4.7-5 Output signals (stVal–Quality) of OR
Input B (stValQuality)
0OK
0NG
1OK
1NG
Input A
(stValQuality)
0OK
0OK
0NG
0NG
0NG
1OK
1OK
1OK
1OK
1NG
1NG
1NG
1OK
1NG
As shown in Table 4.7-5, if ‘0’ represents the status value stVal for all input signals, and
if the quality information of NG is given for an input signal, then the output signal Quality
is represented as NG. On the other hand, if all input signals stVal are represented by 1,
and if the quality information for the input signals stVal(1) is given, then the representation
OK can be weighted for the output signal Quality . Note that quality information (OK) for
input signals with stVal(1) get priority if there are two or more input signals, which are
represented as stVal(1).
Figure 4.7-6 shows the logic symbol for the interlock operator OR with input signals and an
output signal, which can be represented by equations (4.7-13) and (4.7-14).
stVal
Quality
stVal
Quality
OR (+)
Output
Input(A)
Input(B)
stVal
Quality
Figure 4.7-6 Interlock operator (OR) and Input/Output signals
stVal=stVa(A)+stVa(B)
(4.7-13)
Quality=!((stVal(A)!Quality(A))(stVa(B)!Quality(B))+
!(stVal(A)+Quality(A)+stVal(B)+Quality(B)))
(4.7-14)