- 671 -
Two devices can be controlled separately; i.e., the DPSY function has two separate sets of logic
for control (i.e., DPSY01 and DPSY02 functions). For simplicity, only the DPSY01 function is
discussed here; the features in the DPSY02 function are identical to the DPSY01 function.
4.2.1 Select logic for SBO/DIR modes
The user should set scheme switch [DPSY01-CTREN] On prior to DPSY01 operation. Table
4.2-11 shows all of the scheme switches in the DPSY function.
(i) Receiving “select command Closing” from the remote-end
Figure 4.2-1 outlines the reception of the select command ‘Closing’ from the remote- end.
Signal reception
IEC61850
Select command Closing from the remote-end
Select command Open from the remote-end
Select command Closing from the local-end
Select command Open from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Figure 4.2-1 Outline of select command ‘Closing’
Input point required mapping
Figure 4.2-2 shows the select logic when a “Select command closing (Remote-Closing-Control)”
signal is applied to the DPSY01 function.