11.4.2 Requirements in the Master station
In the master station of the IEC 60870-5-103 standard, the following specifications should be
followed in the respective IEDs:
1) Polling cycle: 150ms or longer
2) Timeout time (time to re-sending the request frame to the IED): 100ms
IEC103 master
IED
Data request
Data request
Response frame
Response frame
Polling cycle:
150ms or more
Figure 11.4-1 Ping cycles between the master station and the IED