6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 358 -
2.28.3 Setting
ICD(Function ID: 480001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
ICD-EN
Off / On
-
ICD function scheme switch
Off
ICD-2f
10 - 50
%
Sensitivity of 2f
15
ICD-OC
0.10 -
5.00
0.50 -
25.00
A
Threshold of fundamental current
0.50
2.50
2.28.4 Data ID
Signal monitoring point
ICD(Function ID: 480001)
Element ID
Name
Description
8000001C20
ICD-A
ICD relay element operated (phase-A)
8100001C21
ICD-B
ICD relay element operated (phase-B)
8200001C22
ICD-C
ICD relay element operated (phase-C)
8300001C23
ICD-OR
ICD relay element operated (3-phases OR)